GT824 Oxygen Monitoring Detector

Product Literature

  • Oxygen Deficiency and Enrichment Monitor
  • Intelligent Model
  • Electrochemical Sensor
  • Bright LCD Display
  • 4-20 mA Output
  • Relay Contacts
  • 2 Alarm Set Points
  • Explosion-proof
  • Aluminum Housing
  • Stainless Steel Sensor Housing
  • Replaces Legacy Model GT821

Features and Benefits

  • Oxygen Deficiency and Enrichment Monitoring Detector
  • Two user selectable alarm setpoints (LOW and HIGH) for Oxygen Deficiency, Oxygen Enrichment or both.
  • Maintenance free electrochemical cell sensing element in stainless steel housing
  • Epoxy coated Copper-free aluminum electronics enclosure with viewing window
  • Explosion-proof approved housing for Class I, Group A, B, C, D
  • Bright LCD display of Oxygen concentration by % of volume
  • Reliable, easy to install, simple to maintain and operate
  • Magnetic switch initiates test or calibration sequence
  • On-screen calibration instructions insure error-free results
  • On-screen reminder for calibration and sensor replacement
  • Available up to IP66 rating
  • Alarm and Fault relay outputs for local control
  • 4-20 mA output suitable for connection to external equipment, including PLC’s, SCADA or distributed control systems and voltage-free relay contacts
  • 24 volt DC nominal operating voltage
  • Typical applications include but not limited to laboratories, medical facilities, testing facilities, semiconductor manufacturing, and locations where carbon dioxide or nitrogen gases are used

Product Summary

GT824 Oxygen Deficiency/Enrichment NOVA-Sensor® ELITE continuously displays the percentage of oxygen in the air in large, easy to read characters. A standard 4-20 milliamp circuit transmits the gas reading to other control equipment. The NOVA-Sensor displays an alarm if an oxygen deficiency or oxygen enrichment is detected. Voltage free relay contacts provided for local alarms, ventilation or shutdown of equipment.  Designed to work with the NOVA-5000/VulcanGuard control panel and compatible with other control panels.  Made in the U.S.A.

THE SENSOR

The SST Model GT824 Oxygen Deficiency/ Enrichment NOVA-Sensor® is a completely self-contained device that measures and displays the concentration of oxygen present in a protected area, performs local control functions, and optionally transmits this information to a central control point. Two alarm relays and a fault relay are included.

An electrochemical fuel cell sensing element with a patented diffusion barrier is located inside the stainless steel flameproof housing. The three electrode cell is maintenance free and stable over long periods of time. The capillary diffusion barrier technology results in a direct response to volume concentration. A high reserve of electrochemical activity insures a long life and excellent temperature stability. The performance is relatively unaffected by humidity, provided that conditions are noncondensing.

Each SST NOVA-Sensor ELITE includes a high reliability microprocessor based transmitter/ controller in the associated explosion proof housing. A digital readout continuously displays operating status and the actual concentration of oxygen. The transmitter converts this reading to a standard 4-20 mA signal. This signal may be connected to any remote device with a standard 4-20 mA input. The HIGH and LOW alarm relays operate at user adjustable alarm trip points; either relay may be set to operate above or below the normal oxygen level. The fault relay operates upon loss of power or internal failure of the unit. Relays are suitable for controlling local HVAC or equipment shutdown.

The automatic calibration sequence is easily completed by just one person. The microprocessor stores the results of the calibration in its permanent (non-volatile) memory for use in subsequent operation. There are no screwdriver or other manual adjustments required. During the calibration process, the 4-20 mA and relay outputs from the sensor are normally suppressed. The sensor automatically returns to normal operation when the calibration is complete. During calibration, the technician may optionally activate the built-in comprehensive input/output test sequence (Comp- Test™). During CompTest, the NOVASensor’s analog and relay outputs are not suppressed, thus providing a complete operational check of the overall system.

The Model GT824 is suitable for the most demanding applications. A large body mass insures excellent vibrational characteristics when used for offshore use. Corrosion resistant materials permit uses in most environments.

Architect's and Engineer's Specifications

Oxygen deficiency/enrichment sensing capability shall be provided by electrochemical fuel cell sensors with diffusion barrier contained in a stainless steel housing. The sensing element shall be exposed to the detected gas through a suitable filter. The element shall use a capillary diffusion barrier technology which results in a direct response to volume concentration. The performance shall be relatively unaffected by humidity, provided that conditions are non-condensing. The sensor shall include microprocessor based control electronics which converts the measured gas concentration to the industry standard 4-20 mA signal, plus alarm and fault relay outputs. A continuously reading digital display shall be provided on the sensor, capable of displaying sensor status and the current oxygen concentration in percent. A switch for initiating sensor calibration shall be provided. Calibration shall not require any operator adjustment. All calibration data shall be stored in non-volatile memory in the sensor. Relay and analog outputs shall normally be inhibited during calibration; however, it shall be possible for the calibrating technician to selectively enable outputs when desired. The sensor shall be suitable for offshore use, and the manufacturers data shall so state. Safety Systems Technology Model GT824 Oxygen Deficiency/Enrichment NOVA-Sensor® ELITE, or approved equivalent, shall be supplied.

Technical Specifications and Ordering Information

Technical Specifications

Power Input: 24 volts DC nominal, 110 mA standby, 125 mA in alarm Will operate within specifications at any supply voltage between 16 and 32 volts.
Nominal Range: 0-25% Oxygen
Max Overload: 30% Oxygen
Operating Temperature: -4 to +131 °F, -20 to +55 °C Continuous -4 to +131 °F, -20 to +55 °C Intermittent Recommended Storage: +32 to +68 °F, 0 to +20 °C
Display Resolution: 0.1%
Relay Outputs: Low Alarm (latching or non-latching) High Alarm (latching) Malfunction (non-latching)
Relay Contact Ratings: 6 amps @ 28 VDC or 300 VAC resistive 1/8 HP @ 120/240 VAC
Analog Output: 0 to 20 mA into a load of 600 ohms or less
Output Drift: Less than 2% signal loss per month Typically less than 10% over operating life
Operating Humidity: 0 to 99% Relative Humidity non-condensing
Operating Life of Cell: 2 years Plug-in cell offers easy field replacement
Size: 7.0 inches wide X 5.0 inches high X 4.0 inches deep Includes junction box and sensor
Weight: 5.75 pounds
Approval Code: Class I, Division 1, Groups A, B,C,D

Ordering Information

PART NO. DESCRIPTION
824-1-AL Model GT824 Oxygen Deficiency/Enrichment Monitoring Detector, aluminum
824-1-SS Model GT822 Oxygen Deficiency/Enrichment Monitoring Detector, stainless steel

Optional Accessories

PART NO. DESCRIPTION
851-1 Rain Shield to protect sensor from rain or snow, stainless steel
852-1 Dust Cover with 40 micron filter to protect sensor from airborne dust
854-1 Duct Mounting Assembly for installing sensor in an air duct